Integrate with Existing Applications

Integration with Schneider Electric I/NET

Schneider Electric I/NET sends alerting information via serial line. PageGate uses the GetSerial module to monitor the serial port for incoming alerts.

Configure the GetSerial Module

  1. Open PG Admin. Go to Interfaces — GetSerial — Settings. Check Enabled.
  2. Set Serial Port to the COM port I/NET feeds data into. Mirror I/NET's Baud Rate, Parity, Data Bits, Stop Bits and Handshaking. Leave Init String blank. Click Apply. Enable for all.
  3. Go to GetSerial — Settings — Record:
    Start Pattern: START | Start Offset: 0
    End Pattern: END | End Offset: 0
    Click Apply.
  4. Go to GetSerial — Settings — Recipient. Select Static Recipient. Choose the recipient or group. Click Apply.
  5. Go to GetSerial — Settings — Sender. Select Static Sender. Enter: INET. Click Apply.
  6. Go to GetSerial — Settings — Message:
    Start Pattern: START | Start Offset: 6
    End Pattern: END | End Offset: -4
    Click Apply.

Schneider Electric I/NET integration documentation ↗

Return to Integration Directory