Andover Controls sends alerting information by serial line. PageGate uses the GetSerial module to monitor a serial port for incoming alerts.
To configure Andover Controls to send the alerts, please reference the I/NET documentation: buildingskb.schneider-electric.com ↗
Configure PageGate's GetSerial Module
Open the PG Admin. Go to Interfaces — GetSerial — Settings. Check Enabled.
Set the Serial Port field to match the COM port I/NET is feeding data into.
Set the Baud Rate, Parity, Data Bits, Stop Bits and Handshaking to mirror the values of I/NET. Leave the Init String field blank. Click Apply. Enable for all groups and recipients.
Go to
GetSerial — Settings — Record:
Start Pattern: START | Start Offset: 0
End Pattern: END | End Offset: 0
Click
Apply.
Go to GetSerial — Settings — Recipient. Select Static Recipient. Select the recipient or group. Click Apply.
Go to GetSerial — Settings — Sender. Select Static Sender. Enter: INET. Click Apply.
Go to
GetSerial — Settings — Message:
Start Pattern: START | Start Offset: 6
End Pattern: END | End Offset: -4
Click
Apply.